Model Number: AW-ATD2188-17
Brand Name: ASENWARE
Key Specifications/Special Features:
Product overviewAW-ATD2188 addressable heat detector (detector hereunder) is a mated product of the 2188/2100 series fire alarm control panels. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding.The detector realizes real-time acquisition of the in situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routing inspection, the detector indicator will blink.When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from thedetector, and the detector indicator will light at the same time to indicate a fire alarm.The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.Product features
We usually deliver products by DHL, PUS, FedEx, or Air.
Product parameters
- It can realize electronic coding and rewrite the address via coder in situ.
- Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation.
- It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
- Non-polarity, two-bus connection that ensures convenient installation and maintenance.
- Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
We usually deliver products by DHL, PUS, FedEx, or Air.
Product parameters
Model No | AW-ATD2188 |
Executive standard | GB4716-2005 |
Operating Voltage | 24V (Pulse Modulation) |
Wiring Method | Non-polarity two-bus addressable system (L1,L2) |
Operating Current | <300 μA (Monitoring Status); or <1.5 mA (Alarm Status) |
Operating Environment | Indoor |
Temperature | -10℃ to +50℃ |
Relative Humidity | ≤95% (40℃±2℃, without condensation) |
Protection Area | ≤60 sq.m |
Installation Height | ≤12m |
Coding mode | It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection. |
Work indication | The red indicator will blink in the monitoring status orremain lit in the alarm status. |
Size ( With Base) | Diameter:100mm; Height: 56mm |
Weight | About 47g |
Shell Material | Hard Plastics |
Shell Color | White or customized |
Service | ODM, OEM is available |
Applicable Places | School; Factory; Office; Dormitory; Hospital; Super Market etc |